Elettrico

StrongCor – Corrugated cable Conduit

2026-11-09T17:26:52+01:00

StrongCor – Corrugated cable Conduit

GENERAL PRODUCT DESCRIPTION

Double-wall corrugated polyethylene conduit, manufactured by continuous coextrusion of the two walls, black in color with a red coextruded band.

Packaged in rolls of 25 or 50 meters, complete with a coupling sleeve and a pre-inserted pull cord.

The cable protection is in compliance with the EN 50626-1 standard, certified by the accredited IMQ institute, bear the CE mark, and have an impact resistance classification of Series N and a crush resistance greater than 750 N.

MAIN FEATURES

  • APPLICATION Protection of low-voltage (LV) electrical cables;
  • CONSTRUCTION Additional UV-stabilizing additives
  • BENDING RADIUS 15 times the outer diameter
  • OPERATING TEMPERATURE RANGE -5 °C / +60 °C
  • INSTALLATION Underground in a trench
  • WARRANTY One year from the date of manufacture indicated on the tube
  • ELECTRICAL RIGIDITY Excellent

Upon request, this type of piping can also be equipped with a Pipe Tracer system, making it:

  1.  traceable with high planimetric and altimetric precision
  2. referenceable (containing information regarding the type of service and its management)

For more information, visit the page ==> CLICK HERE

CERTIFICATES:

ITALIANA CORRUGATI

IMQ - 750N

IPPR Cert. 1940/2021

PVC CABLE COVER (PROTECTIVE TILE) FOR UNDERGROUND CABLE PROTECTION – ENEL DS4 SERIES

2026-10-06T12:49:05+02:00

PVC cable cover (protective tile) for underground cable protection – ENEL DS4230 series

GENERAL PRODUCT DESCRIPTION

The ash-grey PVC material is resistant to chemical agents commonly found in the soil (saline water, hydrocarbons). The cable covers feature a virtually constant thickness across their entire cross-section; the ribs must be positioned at least 20 mm from the edges. The cable covers are equipped with an interlocking system designed to
pass the tests specified in ENEL standard 4831. This interlocking system must be integral to the unit (requiring no additional components) and must allow for a
continuous deviation of the installation axis of at least 30° while maintaining the overlap of the ends of two adjacent elements; under standard straight-line
installation conditions, the overlap must be between 50 and 60 mm.

CABLE COVER (PROTECTIVE TILE) USAGE

Cables are typically laid above conduits (cable ducts) or directly into the ground within an open trench on a prepared bedding layer.
In both installation scenarios, the following is required:
• additional mechanical protection (cable duct or synthetic resin element); • a warning tape (bearing the inscription “ENEL CAVI ELETTRICI” / “ENEL ELECTRIC CABLES”)
In this regard, the correct positioning of these two elements is crucial to prevent accidental contact with or damage to the cables during work performed in their vicinity. Supplementary cable protection is not required in the following cases:
• MV cables laid at a depth greater than 1.7 m
• LV cables laid at a depth greater than 0.5 m, provided they are of the concentric neutral type with solid extruded insulation made of G7-type ethylene-propylene rubber or cross-linked polyethylene (XLPE).

MAIN APPLICATIONS

The following types of cable ducting/conduit arrangements are specified:
• Type A: depth from 0.6 to 1.00 m
• Type B: depth from 1.00 to 1.40 m
• Reduced depth: depth from 0.40 to 0.50 m
Type B installations are intended for public roads, where the new Highway Code mandates a minimum depth of 1 m from the top of the cable assembly. Type A installations are intended for private roads and all other areas, where the minimum depths established by the CEI 11-17 standard apply. Reduced-depth installations are permitted only in exceptional cases upon specific request by ENEL.

KEY FEATURES

» Color: Grey
» Weight: 1.4 / 1.55 kg
» Hardness: 90 / 98 Shore A
» Material: Self-extinguishing PVC
» Operating temperature: -60° to +50°C
» Thermal conductivity: 3.5 / 4
» Fire behavior: Self-extinguishing

Single Wall corrugated Pvc Pipe FlexCor

2026-10-28T15:03:52+01:00

Single Wall corrugated Pvc Pipe FlexCor

FlexCor fl exible ducting for electrical systems
Designed specifi cally to optimise building installations, the new, single wall ducting pipe combines high structural fl exibility with maximum on-site logistic effi ciency, guaranteeing impeccable protection and rapid installation.

TECHNICAL CHARACTERISTICS MATERIAL
high quality, PVC based thermoplastic
GEOMETRY
single wall, corrugated pipe, without wire puller
SAFETY
self-extinguishing and highly fl ame-resistant
CONFORMITY
constructed in conformity with the strictest safety standards for the building sector and certifi ed with the Quality Mark

OPERATIONAL ADVANTAGES LOGISTIC OPTIMISATION
supplied on high density pallets to reduce storage space and shipping costs
ON!SITE PRACTICALITY
light-weight, compact rolls (100m, 50m and 25m) that facilitate unpacking and reduce material waste
EXCELLENT FLEXIBILITY
optimal curve radius to deal easily with structural corners without choke points

Contact Us

    Privacy Policy

    1)* I declare I read the Privacy policy of this website.
    2) We would like to use your personal data in order to keep you update through e-mails, instant messages, chats or phone calls on news and commercial offers concerning our products and services and the third parties ones, and also concerning other marketing activities mentioned in the C letter. Please note that you can always change your decision and refuse the processing of your personal data for marketing purposes by contacting us through the e-mail address privacy.systemgroup@tubi.net .